19

Function library

19.1

Function blocks

1652

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Required parameter settings
For an error-free function of the sequence control, the following parameter settings are required for

the FB

L_MckCtrlInterface_1

:

19.1.158.2 Priorities of the control signals

The boolean control signals have the following priorities (1 = highest priority):
1. bReset

2.

bBreak

3.

bPause

4.

bStart

5.

bCancel

Parameter

Info

MCK operating mode at profile no. 0

(

C01298/1

)

Selection of the operating mode for profile 0 ... 15 at

L_MckCtrlInterface_1.

For these four parameters, set the selection "0: No

change" (no assignment of an operating mode to a

profile).

MCK operating mode at profile no. 1

(

C01298/2

)

MCK operating mode at profile no. 2

(

C01298/3

)

MCK operating mode at profile no. 3...15

(

C01298/4

)

L_MckCtrlInterface_1: Alternative function

(

C01297

)

Bit coded selection of the

Alternative functions

for the

bit 16 (PosExecute) in the MCK control word.

For this parameter, set the hexadecimal value "0x0" to

deactivate all alternative functions.