2 setting the error response, Setting the error response, 10 diagnostics & error management – Lenze 8400 TopLine User Manual

Page 691

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

691

10

Diagnostics & error management

10.6

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10.6.2

Setting the error response

When a monitoring function responds, the response set for this monitoring function (TroubleQSP,

Warning, Fault, etc.) will be triggered.

• For many monitoring functions the response can be individually parameterised via parameters.

Tip!
The table in the chapter "

Short overview (A-Z)

" contains the error messages for which the

response can be set.

( 702)

Warning thresholds
Some of the monitoring functions are activated if a defined warning threshold (e.g. temperature)

has been exceeded.

• The corresponding preset threshold values can be changed via the following parameters:

Parameter

Info

C00120

Setting of motor overload (I²xt)

C00123

Device utilisat. threshold (Ixt)

C00572

Brake resistor overload threshold

C00599

Motor phase failure threshold

Advertising