C00431 | ls_multiencoder: bfail selection, N in, C00431/1 – Lenze 8400 TopLine User Manual

Page 975: 17 parameter reference

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

975

17

Parameter reference

17.2

Parameter list | C00431

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00431

Parameter | Name:

C00431 | LS_MultiEncoder: bFail selection

Data type: UNSIGNED_16

Index: 24144

d

= 5E50

h

From version 13.00.00

Bit coded setting which events cause the bFail output to be set.
Setting range

(min. hex value | max. hex value)

0x0000

0xFFFF

Value is bit-coded:

Info

Bit 0 Encoder open circuit
Bit 1 KTY open circuit
Bit 2 Position beyond C1112/2..3
Bit 3 Angular drift error
Bit 4 Communication error
Bit 5 Hiperface position invalid

From version 14.00.00

Bit 6 Linear data overflow SSI

From version 14.00.00

Bit 7 Max. encoder speed

From version 14.00.00

Bit 8 Hiperface init active
Bit 9

Reserved

Bit 10

Reserved

Bit 11

Reserved

Bit 12

Reserved

Bit 13

Reserved

Bit 14

Reserved

Bit 15

Reserved

Subcodes

Lenze setting

Info

C00431/1

0x001D

LS_MultiEncoder

: bFail selection

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT