C00583 | resp. to motor temperature kty, C00585 | resp. to motor overtemp. ptc, C00586 | resp. to open circuit htl encoder – Lenze 8400 TopLine User Manual

Page 1014: C00585, Is activated, Tting, Fault"), mo, C00586, Deactivate the monitoring, C00583/1

Advertising
background image

17

Parameter reference

17.2

Parameter list | C00583

1014

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00583

C00585

C00586

Parameter | Name:

C00583 | Resp. to motor temperature KTY

Data type: UNSIGNED_8

Index: 23992

d

= 5DB8

h

Response to motor overtemperature

• The motor temperature is measured via the resolver or encoder cable.

Encoder/feedback system: Motor temperature monitoring (KTY)

Selection list

0 No Reaction
1 Fault
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information

Subcodes

Lenze setting

Info

C00583/1

1: Fault

Resp. to motor overtemp. KTY resolver

C00583/2

1: Fault

Resp. to motor overtemp. KTY MultiEncoder

C00583/3

5: Warning

Resp. to motor temp. > C00121 resolver

C00583/4

5: Warning

Resp. to motor temp. > C00121 encoder

C00583/5

1: Fault

Resp. to temp. sensor error KTY resolver

C00583/6

1: Fault

Resp. to temp. sensor error KTY MultiEncoder

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00585 | Resp. to motor overtemp. PTC

Data type: UNSIGNED_8

Index: 23990

d

= 5DB6

h

Response to motor overtemperature

• The motor temperature is measured by means of a PTC thermistor at terminal X106.

Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
5 Warning

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00586 | Resp. to open circuit HTL encoder

Data type: UNSIGNED_8

Index: 23989

d

= 5DB5

h

Response to encoder feedback system failure or encoder feedback system track failure due to open circuit
Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
5 Warning

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Advertising