6

Encoder/feedback system

6.3

Multi-Encoder (X8)

328

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.3.2

SinCos absolute value encoder with HIPERFACE® protocol

SinCos absolute value encoders with HIPERFACE® protocol are feedback systems which transmit an

absolute position on request. Moreover, they permanently provide an incremental signal via a

sin/cos evaluation. The analog evaluation of the sin/cos tracks provides for a high resolution.
The absolute position is transmitted via an RS485 data interface with 9600 Baud (standard

value).This bidirectional parameter channel also serves to request and transmit error codes, encoder

data and other information. The analog process data channel is created by a differential

transmission of sin/cos signals. The resolutions of these two information channels are generally not

identical, thus the channels have to be parameterised independently of each other in the controller.

6.3.2.1

Initialisation

A connected SinCos absolute value encoder with HIPERFACE® protocol is initialised in the following

cases:

A. When the device is switched on after the waiting time of approx. 1 s has expired.
B. After the encoder wire breakage has been removed.

In case of an encoder wire breakage, a speed and position detection cannot be carried out

correctly. A renewed initialisation after removing the encoder wire breakage serves to connect

to the correct absolute position.

C. After describing one of the following parameters as the setting has an impact on the internal

scaling of the encoder position:

Note!

If the RS485 cable is interrupted, a communication to the encoder is permanently tried

to be built up. After the maximum initialisation time set in

C00430/1

has expired, the

error "

Sd7: Error encoder communication

" is triggered. This error is cancelled if a

communication could be built up successfully and the encoder initialisation has been

executed.
The selection of an error response in

C00603/4

serves to optionally monitor the

communication between absolute value encoder and controller.
If the monitoring is tripped:

• The error response set in

C00603/4

is triggered.

• The "

Sd7: Encoder communication error

" error message is entered into the logbook.

Parameter

Name

Parameter

Name

C00420/3

LS_MultiEncoder: Encoder increment

C00495

Speed sensor selection

C00422

LS_MultiEncoder: Encoder type

C01110

LS_MultiEncoder: Solid measure

C00490

Position encoder selection

C01111/1..3

LS_MultiEncoder: Encoder constant

C00494/1..2

Hiperface: Resolutions

C01204

MCK: Feed constant