Output → clt- 1cn-26 – Yaskawa DR2 Sigma Servo User Manual

Page 148

Advertising
background image

3.7 Forming a Protective Sequence

135

Output CLT+ 1CN-25

Speed Coincidence Output

For Speed/Torque

Control Only

Output CLT- 1CN-26

Speed Coincidence Output

For Speed/Torque

Control Only

For speed/torque control only.

This output signal indicates that actual motor
speed matches the input speed reference during
speed control.

ON
status:

Circuit between 1CN-25 and 1CN-26 is
closed.
1CN-25 is at low level.

Actual motor speed matches the speed
reference (speed difference is below the
preset value).

OFF
status:

Circuit between 1CN-25 and 1CN-26 is
open.
1CN-25 is at high level.

Actual motor speed does not match the
speed reference (speed difference is
greater than the preset value).

Preset value: Cn-22 (speed coincidence signal output width)

2) Set the following user constant to specify the output conditions for speed coincidence

signal V-CMP.

Cn-22

VCMPLV Speed Coincidence

Signal Output Width

Unit:

r/min

Setting

Range: 0

to Max.

Speed

Factory

Setting:

10

For

Speed/Torque

Control Only

For speed/torque control only

Set the output conditions for speed coincidence
signal V-CMP+ (1CN-25).

V-CMP+ signal is output when the difference be-
tween the reference speed and actual motor
speed is not greater than the preset value.

Example: When preset value is 100 and reference speed is 2000 r/min.

V-CMP+ is ON (circuit between 1CN-25 and 1CN-26 is closed) when the speed is be-
tween 1900 and 2100 r/min.

3

Motor

speed

Reference

speed

V-CMP+ is output

within this range.

Motor

speed

Reference

speed

V-CMP+ is out-

put within this

range

Advertising