INSPECTION, MAINTENANCE, AND TROUBLESHOOTING

6.2.1 Troubleshooting Problems with Alarm Display cont.

394

Cause

Remedy

A

Wiring grounded between Servopack and

servomotor.

Check and correct wiring.

B

Servopack ambient temperature exceeds

55°C

Bring Servopack ambient temperature to

55°C
Note Alarm cannot be reset while power

transistor module temperature ex-
ceeds 90°C.

C

Servomotor U, V, or W phase grounded.

Replace servomotor.

D

• Circuit board (1PWB) defective
• Power transistor defective

Replace Servopack.

E

Current feedback circuit, power transistor,

DB relay, or circuit board defective.

Replace Servopack.

D

Display and Outputs

Digital Operator

Di l

d

Alarm Output

g

p

Display and

Alarm Name

Alarm Code Output

Alarm Output

Alarm Name

ALO1

ALO2

ALO3

p

A.20

Fuse blown

OFF

ON

OFF

OFF

OFF: Output transistor is OFF
ON: Output transistor is ON

Status When Alarm Occurred

A

At control power ON

At main circuit power ON

B, C

Cause

Remedy

A

Circuit board (1PWB) defective

Replace Servopack.

B

Fuse is blown.

Replace Servopack.

C

Main circuit diode module defective

Replace Servopack.

D

Display and Outputs

Digital Operator

Di l

d

Alarm Output

g

p

Display and

Alarm Name

Alarm Code Output

Alarm Output

Alarm Name

ALO1

ALO2

ALO3

p

A.31

Position error

pulse overflow
(position control

only)

ON

ON

OFF

OFF

OFF: Output transistor is OFF
ON: Output transistor is ON