APPLICATIONS OF Σ-SERIES PRODUCTS

3.1.3 Restricting Torque cont.

58

User Constant Setting:

Memory switch (Cn-01) bit 4 = 0

Sets the maximum torque values for
forward rotation and reverse rotation,

respectively.
Sets these user constants when torque
must be restricted according to ma-

chine conditions.
This torque restriction function always
monitors torque, and outputs the signal

shown on the right when the limit value

is reached.
Specifies a torque limit value in terms of

a percentage of the rated torque.

Output Signal for Torque Restric-
tion Function

D

CLT+ (1CN-25), CLT- (1CN-26)

D

Status indication mode bit data

D

Monitor mode (Un-05) bit 4

Example of Use: Machine Protection

Motor speed

Torque limit

Torque

Note that too small a torque limit val-
ue will result in torque shortage at ac-

celeration or deceleration.

• Using CLT+, CLT- Signals

This section describes how to use contact output signals CLT+, CLT- as a torque limit
output signal.

Photocoupler Output

Per output:

Maximum operation

voltage: 30 VDC
Maximum output

current: 50 mA DC

Servopack

I/O power

supply

+24V

1CN-25

1CN-26

CLT+

CLT-

Output CLT+ 1CN-25

Torque Limit Output (Running

Output)

For Speed/Torque

Control

Output CLT- 1CN-26

Output)

Control

This signal indicates whether motor output torque (current) is being restricted.

ON status: The circuit between 1CN-25 and

1CN-26 is closed.

1CN-25 is at low level.

Motor output torque is being restricted.

(Internal torque reference is greater than the

preset value.)

OFF status: The circuit between 1CN-25 and

1-CN26 is open.

1CN-25 is at high level.

Motor output torque is not being restricted.

(Internal torque reference is equal to or below

the preset value.)