A.02 – Yaskawa DR2 Sigma Servo User Manual

Page 404

Advertising
background image

INSPECTION, MAINTENANCE, AND TROUBLESHOOTING

6.2.1 Troubleshooting Problems with Alarm Display cont.

392

Cause

Remedy

A

Absolute encoder power not supplied from

Servopack.

Use the Servopack power supply for the

absolute encoder.

B

Incorrect absolute encoder wiring (PA, PB,

RESET, SEN signal (for speed control),

etc.)

Check and correct the absolute encoder

wiring.

C

Absolute encoder malfunctioned

• When Cn-01 Bit 1 = 0, turn SEN signal OFF

and back ON. (See note)

• When Cn-01 Bit 1 = 1, turn Servopack con-

trol power OFF and back ON.

D

Incorrect user constant setting.

Incremental encoder used with Cn-01 Bit E

set to 1.

Set Cn-01 Bit E to 0.

E

Absolute encoder defective

Replace servomotor.

F

Circuit board (1PWB) defective

Replace Servopack.

NOTE

Resetting SEN Signal
When resetting the SEN signal (i.e., turning it OFF and then back ON) for any reason, keep
the SEN signal at the high level for more than 1.3 s before turning it OFF.

SEN signal

OFF

ON = High Level

1.3 s min.

OFF ON

15 ms min.

D

Display and Outputs

Digital Operator

Di l

d

Alarm Output

g

p

Display and

Alarm Name

Alarm Code Output

Alarm Output

Alarm Name

ALO1

ALO2

ALO3

p

A.02

User constants

breakdown

OFF

OFF

OFF

OFF

OFF: Output transistor is OFF
ON: Output transistor is ON

Status When Alarm Occurred

At control power ON

A

,

B

Cause

Remedy

A

Power turned OFF during parameter write.

Alarm occurred next power ON.

Replace Servopack.

B

Circuit board (1PWB) defective

Replace Servopack.