2.4 Conducting a Test Run

39

2.4.2 Step 1: Conducting a Test Run for Motor without Load

Check that the motor is wired correctly.
If the motor fails to rotate properly during a servo drive test run, the cause most frequently lies
in incorrect wiring.
Conduct a test run for the motor without load according to the procedure described below.
For customers who use a servomotor with brake, refer to Section 2.4.4 Supplemental In-
formation on Test Run
before starting a test run.

Operate the motor with

a Digital Operator.

Check wiring.

Do not connect to the machine.

(1) Secure the servomotor.

Secure the servomotor to mounting holes to
prevent it from moving during operation. Alter-
natively, install the servomotor on the machine
and disconnect couplings and belts.

(2) Disconnect connector 1CN, then check the

motor wiring in the power supply circuit.

(When incremental encoder is used)
I/O signals (1CN) are not to be used so leave
connector 1CN disconnected.

(When absolute encoder is used)
Connect the battery to the battery terminals
1CN-21, -22.

(3) Short the alarm signal circuit.

Because connector 1CN is disconnected, the
alarm signal prevents the power supply circuit
from being turned ON. Therefore, temporarily
short the alarm signal circuit.

2

Secure servomotor to mounting holes.

Do not connect

anything to the

motor shaft

(no-load

status).

Disconnect

connector

1CN

Power supply

0V +24V

Force this relay ON.

Short this

circuit.

1CN disconnected

ALM+

ALM-

(1CN−31)

(1CN−32)