3.2 Setting User Constants According to Host Controller

79

4) Set the pulse dividing ratio in the following user constant.

Cn-0A

PGRAT

Dividing Ratio Setting

Unit:

P/R

Setting

Range: 16

to No. of

Encoder

Pulses

Factory

Setting:

2048

For Speed/Torque

Control and Position

Control

Sets the number of output pulses for PG output
signals (PAO,

£

PAO, PBO and

£

PBO).

Pulses from motor encoder (PG) are divided by
the preset number of pulses before being output.

The number of output pulses per revolution is set in this user constant. Set this value ac-
cording to the reference unit of the machine or controller to be used.

The setting range varies according to the encoder used.

Motor Type

Number of Encoder Pulses Per Revolution

Setting Range

SGM-jjj31j

SGMP-jjj31j

Incremental encoder: 2048 pulses per revolution

16 to 2048

SGM-jjjW1j

SGMP-jjjW1j

Absolute encoder: 1024 pulses per revolution

16 to 1024

For the user constant Cn-0A, always turn the power OFF and then ON after chang-
ing the setting. This makes the new setting valid.

3

Servomotor

encoder

Servopack

Output terminals:

PAO (1CN-33)

£

PAO (1CN-34)

PBO (1CN-35)

£

PBO (1CN-36)

Frequency

dividing

Phase A

Phase B

Setting example:

Preset value: 16

1 revolution