3.2 Setting User Constants According to Host Controller

73

Input Pulse Multiply Function:

When the reference form is two-phase pulse
train with 90
° phase difference, the input pulse

multiply function can be used.

The electronic gear function can also be used
to convert input pulses.

Example of I/O Signal Generation Timing

Servo ON

Base block

Sign +

pulse train

Release

t1 ≦ 30 ms
t2 ≦ 6 ms

(When user

constant Cn-12 is

set to 0)
t3 ≧ 40 ms

PG pulse

t4, t5, t6 ≦ 2 ms
t7 ≧ 20 μs

Note The interval from the time the servo ON signal is turned ON until a reference pulse is

input must be at least 40 ms. Otherwise, the reference pulse may not be input.

The error counter clear (CLR) signal must be ON for at least 20 μs. Otherwise, it be-

comes invalid.