Section 5A

9/440 Resolver--based CNC/Drive System

5A-33

Grounded vs Ungrounded Three Phase

The 9/440 Resolver--based CNC/Drive comes from the factory set for three

phase grounded systems. If your facility uses an ungrounded three phase

360/480 volt system, you must move a jumper in the 9/440 Resolver--based

system module. This jumper will connect an internal resistor that helps

keep high voltage static, that can be typical of ungrounded three phase

systems, from building up in the system module.

Jumper Setting

Three Phase Power

J27 to J26 (factory setting)

Grounded system

J27 to GND3

Ungrounded systems

Figure 5A.17

Three- phase Jumper

9/440 Resolver--based

System Module

Open cover

J2

6

J2

7

G

N

D

3

Wire Jumper