Resetting an absolute encoder on the 9/230 – Rockwell Automation 8520 9/Series CNC Integration Maintenance Manual Documentation Set User Manual

Page 667

Advertising
background image

Section 13A

Connecting 8520 Digital Drive Systems

13A-33

The turns counter register of an absolute encoder can be reset to zero at

system start up or if the absolute encoder’s battery backup has failed.

Resetting an Absolute Encoder on the 9/230

At the control:

1.

Move the axis that the absolute encoder is configured for in AMP to

the desired zero coordinate position for that axis.

2.

Turn OFF the control and the main ac power switch.

ATTENTION: Never adjust the control unless the main AC

disconnect switch is open (off) and locked.

3.

Disconnect the battery that supplies battery backup to the absolute

encoder being reset.

4.

Determine whether it is easier to disconnect and access connectors at

the servomotor or at the control.

If accessing connectors at the 8500 digital servo motor:

a.

Remove the cable that is connected to the absolute encoder to be

reset.

b.

At the encoder, use a jumper to short pin R to pin S of the

absolute encoder for at least 2 minutes.

A

B

C

D

E

F

G

H

J

L

M

N

P

R

S

T

K

13A.9.3

Resetting Absolute

Encoders on an 8500 Digital

Servo Motor

Advertising