Section 5B

9/440HR CNC/Drive System

5B-34

Figure 5B.20

Recommended Connection of Three- phase Drive Power

Customer Supplied

E-STOP Control Relay

DC+

INT

COL

W1

W2

U

W

V

PE

9/440HR Power Strip

E-STOP

Connector TB1

1

7

E-STOP

status contact

(30V dc 1.4A)

Noise suppressor

Customer supplied

24V Power Supply

Output 24 V ac or

24 V dc

AC Bulletin 100--A30N x 3 (surge protector required) or

DC Bulletin 100--A30NZ x 3

Bussman FRS--R--20A (class RK-5)

600 V AC (qty 3)

Three-phase input

360 or 480V AC

Bulletin 100

Contactor Power

Noise suppressor

Other Customer Controlled

E-STOP Status Relays

Customer

Supplied

Fuse

c

c1

m

m1

m2

m3

ATTENTION: Brake control should not be directly released by

the E-STOP status relay (or your customer supplied E-STOP

control relay). Brakes should only be released by the PAL logic

when it has determined that the 9/440HR is in full control of the

servo motors and the control is out of E-STOP. See the

description of the PAL flag $PFLT.15 for detail on how to test

drive status.