I/O Interface

Section 10A

10A-29

Specifications for hard contact relay outputs are shown below. It is

recommended that some type of noise suppressor be used when switching

inductive load devices with hard contact outputs.

Table 10A.R

Relay Type Output Specifications

Item

Rating

Remark

Voltage Range

10-125 V dc

50/60 Hz

Contact Resistance

20 milliohms

Electrical-optical Isolation

2000 V

Between Output Contacts and Control Logic

Digital I/O types E151, E152, and E154 have 2 hard contact relay outputs,

at terminals A11 and B11. These outputs do not have internal arc

suppression circuitry.

Digital I/O type E153 has 12 hard contact relay outputs. Relay outputs at

terminals A12 through A16 and B12 through B16 have internal arc

suppression circuitry. Relay outputs at terminals A11 and B11 do not have

internal arc suppression circuitry.

Table 10A.S

Contact Ratings

Volts

Amperes

Amperes

Voltamperes

Make

Break Continuous

Make

Break

240 V ac

7.5A

0.75A 2.5A

1800

VA

180 VA

120 V ac

15A

1.5A

125 V dc

0.22A

1.0A

28 VA

24 V dc

1.2A

2.5A

28 VA