Section 7A

Connecting Components

7A-62

Table 7A.A

Cable and Connector List (continued)

Cable No.

Control

From Module and Connector

Cable Name

To Module and Connector

Cat. No.

C55

9/440 (all)

External 380/460V Three Phase

Drive Power

9/440 System Module

Power Terminal Block

Prepared by Customer

dc+

INT

COL

W1

W2

U

W

V

PE

9/440 Power Strip

Noise suppressor

ac Bulletin 100--A30N x 3 (surge protector required) or

dc Bulletin 100--A30NZ x 3

Bussman FRS--R--20A (class RK-5)

600 V ac (qty. 3)

Three-phase input

380-460V ac

Bulletin 100

Contactor Power

C

55

E-Stop Status Contactor

(customer supplied or internal 9/440 TB1 status)

!

ATTENTION: Brake control should not be directly released by the

E-Stop status relay (or your customer supplied E-Stop control relay).

Brakes should only be released by the PAL logic when it has

determined that the 9/440 is in full control of the servo motors and the

control is out of E-Stop. See the description of the PAL flag

$PFLT.15 for detail on how to test drive status.

Connector On End of Cable

Cable Type

Connector on End of Cable

Max. Cable Length

Miscellaneous

See Local Codes

(12Awg max)

Clamped by terminal screws

Line Drop Limitation