Rockwell Automation 8520 9/Series CNC Integration Maintenance Manual Documentation Set User Manual
Page 410

Section 7A
Connecting Components
7A-62
Table 7A.A
Cable and Connector List (continued)
Cable No.
Control
From Module and Connector
Cable Name
To Module and Connector
Cat. No.
C55
9/440 (all)
External 380/460V Three Phase
Drive Power
9/440 System Module
Power Terminal Block
Prepared by Customer
dc+
INT
COL
W1
W2
U
W
V
PE
9/440 Power Strip
Noise suppressor
ac Bulletin 100--A30N x 3 (surge protector required) or
dc Bulletin 100--A30NZ x 3
Bussman FRS--R--20A (class RK-5)
600 V ac (qty. 3)
Three-phase input
380-460V ac
Bulletin 100
Contactor Power
C
55
E-Stop Status Contactor
(customer supplied or internal 9/440 TB1 status)
!
ATTENTION: Brake control should not be directly released by the
E-Stop status relay (or your customer supplied E-Stop control relay).
Brakes should only be released by the PAL logic when it has
determined that the 9/440 is in full control of the servo motors and the
control is out of E-Stop. See the description of the PAL flag
$PFLT.15 for detail on how to test drive status.
Connector On End of Cable
Cable Type
Connector on End of Cable
Max. Cable Length
Miscellaneous
See Local Codes
(12Awg max)
Clamped by terminal screws
Line Drop Limitation