Section 13A

Connecting 8520 Digital Drive Systems

13A-16

Table 13A.G through Table 13A.L list the 8520 digital servo amplifier

jumper settings. These jumpers are used to configure the 8520 digital

servo amplifier to supply 200% or 300% of the motor rated current, enable

or disable the servo motors, latch or unlatch the bus under voltage fault

detector, and select the internal or external shunt resistor.

ATTENTION: Incorrect jumper settings can cause damage to

the servo motors and/or servo amplifiers.

Table 13A.G

1AX-D (1 axis) Servo Amplifier Jumper Settings

Axis 1 - - CNA1

J1

J2

J3

J4

J7

J8

J9

J10

Motor Rated Current

200%

300%

1.3

1.3

2.6

2.6

·

·

3.9

3.9

·

·

5.2

5.2

·

·

·

·

6.5

6.5

·

·

7.8

7.8

·

·

·

·

9.1

9.1

·

·

·

·

10.4

10.4

·

·

·

·

·

·

11.8

11.8

·

·

13.1

13.1

·

·

·

·

14.4

>AMP Limit

·

·

·

·

15.7

>AMP Limit

·

·

·

·

·

·

17.0

>AMP Limit

·

·

·

·

18.3

>AMP Limit

·

·

·

·

·

·

19.6

>AMP Limit

·

·

·

·

·

·

20.9

>AMP Limit

·

·

·

·

·

·

·

·

·

” Denotes jumper short

For 200% of motor rated current, the following jumpers are shorted:

- AXIS 1: J5, J6, J11, J12

For 300% of motor rated current, the following jumpers are open:

- AXIS 1: J5, J6, J11, J12

13A.5

8520 Digital Servo Amplifier

Jumper Settings