Section 13A

Connecting 8520 Digital Drive Systems

13A-35

Resetting an Absolute Encoder on the 9/260 and 9/920

Important: The following procedure is no necessary if you are using

distance--coded markers or a Stegmann feedback device.

At the control:

1.

Move the axis that the absolute encoder is configured for in AMP to

the desired zero coordinate position for that axis.

2.

Turn OFF the control and the main ac power switch.

ATTENTION: Never adjust the control unless the main AC

disconnect switch is open (off) and locked.

At the servo module:

1.

Disconnect the battery that supplies battery backup to the absolute

encoder being reset.

2.

Determine whether it is easier to disconnect and access connectors at

the servomotor or at the servo module.

If accessing connectors at the 8500 digital servo motor:

a.

Remove the cable that is connected to the absolute encoder to be

reset.

b.

At the encoder, use a jumper to short pin R to pin S of the

absolute encoder for at least 2 minutes.

A

B

C

D

E

F

G

H

J

L

M

N

P

R

S

T

K

11294-I