10 mms ethernet communications – Rockwell Automation 8520 9/Series CNC Integration Maintenance Manual Documentation Set User Manual

Page 462

Advertising
background image

CNC Processor Board

Serial

Port A

Video

Front of

System Module

R--I/O

LED

Section 8

Communication Interface

8-29

9/440 Remote I/O LED

Assuming you have:

made all necessary remote I/O communication connections on your
1771 I/O network

configured your remote I/O port for the remote I/O network in AMP

written PAL to set $RMON true during the first PAL foreground
execution, and to handle input and output words ($RMI1 -- $RMI8

inputs to PAL and $RMO1 -- $RMO8 outputs from PAL.)

You are ready to start receiving and transmitting remote I/O information.

An LED is provided on the 9/440 CNC processor board and is visible from

the bottom of the system module. As remote I/O responds to commands,

you should see this LED pattern:

LED

Status

Description

Green

R- I/O LED

ON

Active Link to PLC. This is the normal state when the

RIO link is active.

FLASHING

The remote I/O link is active but the PLC is currently in

program mode.

OFF

Remote I/O link is offline. The port is not being used,

not configured in AMP correctly, not turned on with

$RMON, or not attached to a 1771 device.

The 9/260 and 9/290 CNCs have an MMS Etherent communications
module available that provide MMS Ethernet services. With this module,

the software is pre--installed with a set of default communication settings

(modifications to these defaults is performed with Allen-Bradley Station

Manager software).

A wide range of services are supported that allow you access to PAL and

control variables, part program management, CNC status, etc... Details on

the MMS Ethernet communications module are provided in a separate

9/Series MMS/Ethernet Communication Module Users Manual (Catalog

number 8520-ENETM). Refer to this publication for further details.

8.10

MMS Ethernet

Communications