Section 7C

Power Distribution and Wiring Guidlines

7C-7

Inductive Load Noise Suppression

Select the noise suppressor according to load size and applied voltage.

Connect the noise suppressor as close to the load as possible.
For a small ac inductive load, such as a solenoid operated by a pushbutton

switch or a limit switch, connect the RC circuit as shown in Figure 7C.7.

Figure 7C.7

Small AC Inductive Load

Small AC inductive load voltage

Load

C

R

11243-I

For a large ac inductive load, such as a motor operated by a contactor,

connect a varistor in parallel with the RC circuit as shown in Figure 7C.8.

Figure 7C.8

Large AC Inductive Load

Large AC inductive load voltage

Load

C

R

Varistor

11244-I