Section 2A

Planning Your System Layout

2A-10

Installing Servo Modules

Digital and analog servo modules include processors that make them very

sensitive to electrical noise. These modules must be placed more than 100

mm (4 in) away from devices and cables to which any AC voltages or DC

voltages greater than 50 Vdc are applied.

Installing Operator Panels

You must place the Operator Panel more than 300 mm (12 inches) away

from devices (transformers, main AC, electromagnetic contactors, etc.)

that generate magnetic fields to protect the CRT display from any possible

adverse effects.

However, a strong magnetic field generated by multiple devices can have

an adverse effect on the CRT display even if the operator panel is placed

more than 300 mm away from these devices. If this occurs, shield the

operator panel from the devices using an electromagnetic and electrostatic

shield plate.

Installing Servo Amplifiers

If you are installing analog servo amplifiers, refer to documentation that

came with your amplifiers for specific installation instructions.

If you are using digital servo amplifiers, place them vertically so that

cooling air can flow upward and remove heat efficiently. Figure 2A.4 and

Figure 2A.5 show the digital servo amplifier installation and spacing

restrictions.

If you are installing digital or analog servo amplifiers in the same cabinet

as the control chassis (excluding the 9/440), then separate the amplifiers

and the control chassis with a grounded, metallic plate to shield the control

from electrical noise. You can use a cabinet with a center divider, where

the power transformers and servo amplifiers are installed on one side, and

the control, operator panel, and I/O modules installed on the other side.

Advertising