Section 13A

Connecting 8520 Digital Drive Systems

13A-10

Table 13A.L

3AX-D Servo Amplifier Terminal Block TB1 Terminal Assignments

Term. No. Connection

Term. No. Connection

1

3

f

200v/230v-

f

1

10

Motor 2-

f

A

2

3

f

200v/230v-

f

2

11

Motor 2-

f

B

3

3

f

200v/230v-

f

3

12

Motor 2-

f

C

4

1

f

200v/230v-1

f

-1

13

Motor 2-F Ground and Shield

5

1

f

200v/230v-1

f

-2

14

Motor 3-

f

A

6

Motor 1-

f

A

15

Motor 3-

f

B

7

Motor 1-

f

B

16

Motor 3-

f

C

8

Motor 1-

f

C

17

Motor 3-F Ground and Shield

9

Motor 1-F Ground and Shield

Table 13A.M

3AX-D Servo Amplifier Terminal Block TB2 Terminal Assignments

Term. No.

Connection

1

DC+

2

DC-

3

Shunt

4

External

Table 13A.N

3AX-D Servo Amplifier Terminal Block TB3 Terminal Assignments

Term. No.

Connection

1

SYSTEM READY (Contact Output)

2

SYSTEM READY (Contact Input)

Typically TB3 is used as a relay in your E-STOP string. Terminal 1 and

Terminal 2 is in a closed connection when the drive is operating correctly

and in an open connection when the drive is in a fault condition.

Table 13A.O

System Ready Contact Ratings

DC

AC

up to 24V max.

up to 1.4 A

up to 30 Watts max.

up to 230V max.

up to 1.4 A

up to 30 Watts max.