Table 10A.AK
1746I I/O Ring Adapter Node Address Setting
Node Address
Switch Assembly Position
Hexadecimal
Binary
1
2
3
4
00
0000
OFF
OFF
OFF
OFF
01
0001
OFF
OFF
OFF
ON
02
0010
OFF
OFF
ON
OFF
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
0F
1111
ON
ON
ON
ON
Important: Switch 5 and 6 of S1 must remain in the OFF position for
normal operation.
The following are the specifications and wiring instructions for the 1746
P1 power supply.
Set the Input Voltage Jumper
1.
Locate the input voltage jumper. If necessary, remove and reinstall
the jumper to match the external voltage available.
ATTENTION: Set the input jumper before applying power.
Hazardous voltage is present on exposed pins when power is
applied: contact with the pins may cause injury to personnel.
push latch up from underneath
to open the door
100/120 V
200/240 V
10A.6.3
1746P1 Power Supply