Section 10B

9/Series Adapter Modules for

1771 and 1746 I/O Devices

10B-10

This section provides diagnostic information for troubleshooting your 1746
I/O chassis using the LEDs on the front of the 1746I module. Also in this

section is information on using test modes to diagnose any problems with

the fiber-optic connections.

OFF

ON

Flashing

This LED Status

Indicates this possible cause:

Run LED On

·The I/O ring and the 1746 I/O rack are

communicating properly and the rack is

functioning.

Rack LED On

·RAM or ROM failure at power turn on.
·Device in rack failed or is not seated properly.
·Internal error in the 1746I adapter.

Rack LED Flashing

·A card type was found in the rack at power turn

on that is not supported by the 1746I module.

Ring LED On

·Connection or device has failed in the I/O ring for

a device before the 1746I in the ring.

·Power turned off at the CNC.
·Transmitter and receiver cables are reversed.

Ring LED Flashing

·Connection or device has failed in the I/O ring for

a device after the 1746I in the ring.

All LEDs Off

·Power turned off at the CNC while the ring was

up and running.

·Connection of I/O ring broken before this 1746I

module while the ring was up and running.

Use this section to calculate the number of ASRN chips used by the 1771
or 1746 I/O chassis in your system. Each chassis uses a different number

of ASRN chips depending on the size of the chassis and the number and

types of I/O devices in the chassis.

Each different 9/Series control supports a limited number of ASRN chips

on its I/O ring. Refer to Table 10A.B for the number of ASRN chips

supported on the ring for your specific 9/Series processor.

10B.2.5

Troubleshooting the 1746I

Communication Module

10B.3

1771 and 1746 I/O adapter

ASRN Use