15a.8 serial i/o diagnostics – Rockwell Automation 8520 9/Series CNC Integration Maintenance Manual Documentation Set User Manual

Page 753

Advertising
background image

Section 15A

Troubleshooting the Control

15A-43

When the {SERIAL I/O} softkey is pressed on the Main Diagnostics Menu

screen, the Serial I/O diagnostics screen appears. “SERIAL I/O” appears

on the top line of the screen, along with the “SETUP MODE” message

indicating that the control is in setup diagnostics mode.

Important: If ports A and B are both currently communicating with a

peripheral, pressing the {SERIAL I/O} softkey displays the message

“BOTH PORTS ARE BUSY” on the operator panel CRT. This softkey is

disabled until the ports are no longer communicating.

Figure 15A.18 below shows a typical Serial I/O screen.

Figure 15A.18

Serial I/O Diagnostics Screen

RECV

XMIT

SERIAL I/O

SETUP MODE

SERIAL PORT:

A

DEVICE:

ALLEN-BRADLEY 1770-SB

PORT TYPE

RS232C

BAUD RATE:

1200

PROTOCOL:

LEVEL 2

PARITY:

NONE

STOP BITS:

1

DATA LENGTH:

8

TIMEOUT:

15 SEC

OUTPUT CODE;

N/A

PORT B PORT A PORT B

RECV

XMIT

PORT A

Important: If port B is configured for ODS communication, the

{RECV PORT B} and {XMIT PORT B} softkeys are not be displayed.

This prevents the user from using port B when the control is

communicating with ODS.

When any of the 4 (or 2) softkeys displayed on the Serial I/O diagnostics

screen is pressed, a screen similar to that in Figure 15A.19 is displayed:

15A.8

Serial I/O Diagnostics