Section 2A

Planning Your System Layout

2A-8

For information on noise prevention measures refer to page 7C-1. We

mention them here because these factors should be taken into consideration

during the beginning stages of cabinet design. These noise prevention

measures are covered in that section:

Signal Grounding
Mechanical Shielding
Shielded Cables and Twisted-pair Cables
Separation of Cable Routes
Noise Suppressors

Install the components in the cabinet with at least 100 mm (4 inches) of

clearance between the cabinet side wall and each component to allow air

flow inside the cabinet. Install the components in the cabinet with 50 mm

(2 inches) of clearance between them.

The system installer should also consider any local regulations regarding

component placement within a cabinet.

ATTENTION: Do not install modules above heat generating

devices (transformers, resistors, etc.)

Figure 2A.3 shows the minimum component spacing.

2A.5

Reducing Noise

2A.6

Installing the Components