Section 7C

Power Distribution and Wiring Guidelines

7C-12

Figure 7C.15

Spike Voltage 100V ac (rms) Arc Inductive Load

(528V)

100V ac

SW

L

100mH

0 Volts

0 Amps

dt = 0.7ms

90

°

I

L

3.71A peak

-3.71 A

di = +3.71A

V

L

141 V peak

11236-I

Radiated Noise

Radiated noise reaches the control through the air. The cables and the

metallic frames, of the control, function as antennas that receive electrical

noise from a variety of sources such as ac power lines, welding arcs,

transformers, motors, and radio wave transmission devices.

If a number of electronic components are arranged near the control, the

surrounding air will be filled with radiated noise. The control must be

shielded to protect it from radiated noise. Radiated noise is composed of

three types of noise:

electrostatic induction noise
magnetic induction noise
electromagnetic induction noise