I/O Interface

Section 10A

10A-16

Each push-button MTB panel I/O module must have a unique node address

on the I/O ring. The node address corresponds to a unique address

assigned to each push-button MTB panel I/O module in the I/O assignment

file. The node address is selected by cutting the jumpers located on the

push-button MTB panel I/O module.

Figure 10A.10 shows the location of the node address jumpers on the MTB

I/O module.

Figure 10A.10

Push-Button MTB Panel I/O Module Jumper Positions

+12V dc
GND

OP11

(out)

OP12

(in)

CN51

CN52

I/O ring fault indicator

JPR1

JPR2

Set the node address by cutting the jumper(s) on the push-button MTB

panel I/O module according to Table 10A.J.

Table 10A.J

Push-Button MTB Panel I/O Module Node Address Setting

Node Address

Jumper

Hexadecimal

Binary

JP1

JP2

00

00

Short

Short

01

01

Short

Open

02

10

Open

Short

03

11

Open

Open

The node address may be any number between 00 and 03. You may have a

total of 4 modules with the MTB panel. The same node address can be

used for different types of modules, but may not be used more than once

for a specific type of module.

10A.2.4

Push-Button MTB Panel I/O

Module Node Address

Setting