Section 8

Communication Interface

8-26

Use this table if you see a different LED pattern than shown above.

Indicator

Color/State

Description

Probable Cause

Recommended Action

A

(B is not used)

green/steady

active link

normal operation

none required

red/steady

hardware fault at

processor

hardware error

cycle power. Replace the processor.

Refer to your processor

documentation.

red/blinking

communication break

AMP is not set correctly

reset AMP parameters to

communicate with scanner program

off

remote I/O port is offline

port is not being used

bring remote I/O port on line

ACT

green/steady

active link to 9/Series

CPU

normal operation

none required

off

remote I/O module is not

communicating with

9/Series control

remote I/O module is offline

AMP or PAL is not properly

configured or your remote I/O

network is not configured to

communicate with the module.

FLT1

on

major hardware fault

device has failed

if LED remains on after cycling

power, contact your Allen-Bradley

FLT1

power, contact your Allen-Bradley

sales representative