I/O Interface

Section 10A

10A-41

Different types of I/O devices can have the same node address, but devices

of the same type must each have a unique node address. Each

high--density I/O module is assigned a unique node address in the I/O

assignment file of ODS. This address corresponds to a switch setting on

the high--density I/O module.

Figure 10A.32 shows the location of the node address switch assembly on

the high--density I/O.

Figure 10A.32

High- density I/O Module Switch Assembly Location

Optical connector

OP24 (IN)

Optical connector

OP23 (OUT)

CN61M

CN62M

CN63F

Fuse

DIP switch

I/O Inputs

I/O Outputs

I/O Inputs

I/O Ring

Fault Indicator

BT33

1 2

3 4

5 6

ON

Set the switch assembly to correspond to the node address as shown in

Table 10A.AD.

Table 10A.AD

High- density I/O Module Node Address Setting

Node Address

Switch Assembly Position

Hexadecimal

Binary

1

2

3

4

5

6

00

00 0000

OFF

OFF

OFF

OFF

OFF

OFF

01

00 0001

OFF

OFF

OFF

OFF

OFF

ON

02

00 0010

OFF

OFF

OFF

OFF

ON

OFF

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

3D

11 1101

ON

ON

ON

ON

OFF

ON

3E

11 1110

ON

ON

ON

ON

ON

OFF

3F

11 1111

ON

ON

ON

ON

ON

ON

10A.4.4

High Density I/O Module

Node Address Setting