Section 2A

Planning Your System Layout

2A-9

Figure 2A.3

Minimum Component Spacing to Allow Air Flow in the Cabinet

Enclosure

100 (3.94)

100

(3.94)

100 (3.94)

50 (1.97)

50 (1.97)

100

(3.94)

100

(3.94)

50 (1.97)

mm

(in)

100

(3.94)

50 (1.97)

100 (3.94)

100 (3.94)

9/440 CNC and digital amplifiers

see page 2A-11

Follow the minimum component spacing requirements when designing the

electrical system layout. You can reduce noise by placing the modules at

least 50 mm apart. If this is not possible, install an electrically conductive

metallic shield plate between the units. Place all devices at least 100 mm

from the cabinet walls. For additional information on electrical system

design requirements refer to 4D-1.

ATTENTION: Do not install the control close to equipment,

such as an arc welder, power transformer, or large motor, that

generates high level noise.