Section 15B

Replacement Procedures

15B-8

Flash SIMM U14 is empty or missing

Make sure your flash SIMMs are installed in the correct tracks.

Low voltage on flash sticks

Call Allen-Bradley Support Services.

Module(s) with inconsistent revision level

Retry update. If this does not work, call Allen-Bradley and request a new update utility.

Module(s) with invalid checksum

Retry update.

Unable to write to flash memory

Call Allen-Bradley Support Services.

Unrecoverable error

Call Allen-Bradley Support Services.

The RAM memory on the motherboard stores part programs and tool
offsets. This stored data is kept active by battery backup while system

power is off. The battery backup, which is supplied by a battery pack

(8520-LIBAT) will retain data for approximately six months.

The battery backup is tested on power-up and at four-hour intervals while

system power is on. If battery voltage drops below the replace-battery

reference level during the battery test, the control automatically displays

the warning message “REPLACE MEMORY BACKUP BATTERY” on

the operator panel.

Once the “REPLACE MEMORY BACKUP BATTERY” message is

displayed, it is essential that the batteries be replaced to avoid loss of data.

If battery voltage drops below the battery-dead reference level during the

battery test, the control displays the message “BATTERY FAILURE.”

Data in RAM memory will be lost if power to the control is turned “OFF”

when the battery is dead.

Batteries and battery replacement instructions are included with the battery

replacement kit. Before installing new batteries, use a voltmeter to make

sure that new battery voltage is higher than 3.5V.

The lithium battery contains heavy metals and

must be collected separately from other waste.

15B.2

Replacing the Lithium Battery