I/O Interface

Section 10A

10A-51

Figure 10A.39

1746 I/O Ring Adapter Switch Assembly Locations

S1

1 2 3 4 5 6

ON

Other 9/Series I/O devices (such as an HPG or MTB panel) on the 9/Series

fiber-optic ring can have the same node address as the 1746I module.

However, devices of the same type (multiple 1746I modules) must each

have a unique node address. Each 1746 I/O ring adapter is assigned a

unique node address in the I/O assignment file of ODS (refer to your PAL

reference manual). This address corresponds to switch assembly S1 on the

1746I module.

Set switch assembly S1 to correspond to the node address as shown in

Table 10A.AK.