Section 13A

Connecting 8520 Digital Drive Systems

13A-8

Table 13A.I

2AX-D Servo Amplifier Terminal Block TB3 Terminal Assignments

Term. No.

Connection

1

SYSTEM READY (Contact Output)

2

SYSTEM READY (Contact Input)

Typically TB3 is used as a relay in your E-STOP string. Terminal 1 and

Terminal 2 is an open connection when the drive is in a fault condition and

a closed connection when the drive is operating correctly.

Table 13A.J

System Ready Contact Ratings

DC

AC

up to 24V max.

up to 1.4 A

up to 30 Watts max.

up to 230V max.

up to 1.4 A

up to 30 Watts max.

Table 13A.K

2AX-D Servo Amplifier Terminal Block TB4 Terminal Assignments

Term. No.

Connection

1

TSW1-1 (For Motor 1)

2

TSW1-2 (For Motor 1)

3

TSW2-1 (For Motor 2)

4

TSW2-2 (For Motor 2)

Important: Terminal block TB4 is an optional connector that provides a

convenient connection to the thermal overload switches of the servo

amplifier. This terminal block is typically used to interface the thermal

overload switches with PAL or the system E-STOP string. The servo

amplifier operates normally without any external connections to terminal

block TB4.