Integrating a Split Axis with Deskew

Section 14B

14B-12

When motion requests are made to the master servo, both the slave and

master always move to the same location at the same feedrate except in

two cases:

E-Stop when a skew condition exists

The maximum skew amount is set in AMP with the parameter Excess

Skew Limit. When this skew amount is reached the control is forced

into E-Stop and can not be taken out of E-Stop until the axes are

manually moved so that the skew amount is less than the Excess Skew

Limit set in AMP.

Anytime E-Stop is reset and some skew exists within the skew limit, the

control will automatically eliminate the skew. The control automatically

sends separate positioning commands to the slave servo to drive it to a

position where zero skew exists between the master and slave servos.

When Homing

When homing the split axis, a single home limit switch is used. The

distance from that limit switch to the home position is dependent on the

closest marker position and the value entered for Home Calibration.

The difference between the two home calibration values and the

direction and distance to the closest marker are independent for both

axes. This means they can receive different positioning commands to

reach the home position.

END OF SECTION