Section 2A

Planning Your System Layout

2A-5

Figure 2A.2

Filtered Air Flow In A Fan Cooled Cabinet

Cabinet

temperature between 0°C

and 55°C

Filter

Cooling air

Exhaust air

Servo

Amplifier

Regardless of air conditioner or heat exchanger rating, be sure its blowers

and all other fans provide sufficient internal air flow.

Calculating the Temperature within the Cabinet

If you have a cabinet that contains an Operator Panel, allow for an
increase in ambient temperature of up to +5

°

C (10

°

F). If you have a

cabinet that contains modules other than the Operator Panel, allow for an
increase of up to +10

°

C (20

°

F).

Temperature information needed when designing a cabinet is listed with

the specifications for each module.

Design the cabinet so that temperature rise inside the cabinet, caused by

heat generation of the modules and other units mounted inside, will not

exceed allowable maximums.

Table 2A.B shows the heat generation wattages of each component or