Section 15A

Troubleshooting The Control

15A-44

Figure 15A.19

Serial I/O Diagnostics Screen

START

REPEAT

STOP

XMIT

SINGLE

XMIT

SERIAL I/O

SETUP MODE

SERIAL PORT:

A

DEVICE:

ALLEN-BRADLEY 1770-SB

PORT TYPE

RS232C

PIN

INP

OUT

BAUD RATE:

1200

PROTOCOL:

LEVEL 2

4

RTS

PARITY:

NONE

5

CTS

STOP BITS:

1

6

DSR

The serial I/O parameters shown will vary for each peripheral device. If

the parameters displayed for a specific peripheral device do not match the

default parameters for that device, the message “PARAMETERS DO NOT

MATCH THE DEFAULTS” are displayed on the screen.

If the protocol parameter is set to LEVEL_1, RAW, or DF1, pressing the

{START} softkey will highlight the CTS output signal. Pressing the

{STOP} softkey changes the CTS output signal back to normal display.

If the protocol parameter is set to LEVEL_2 and the control is receiving

data, pressing the {START} softkey displays DC1 on the screen. Pressing

the {STOP} softkey displays DC3.

If the protocol parameter is set to LEVEL_2 and the control is transmitting

data, pressing the {START} softkey displays DC2 on the screen. Pressing

the {STOP} softkey displays DC4.

Important: For more information on protocol, refer to page 8-9.

When the {REPEAT XMIT} softkey is pressed, the control highlights this

softkey and transmits a string of characters that corresponds to last key

pressed on the operator panel keyboard. Pressing any of the softkeys stops

transmission.