I/O Interface

Section 10A

10A-62

If the 9/Series fiber optic I/O ring should fault or any other fault should
occur within the 1746 I/O rack, the 1746I module will attempt to maintain

all of its I/O in the same state condition. This holds all output devices in

the chassis to their present state. (Outputs already ON remain ON, outputs

already OFF remain OFF, and analog modules maintain their present

output voltage).

Wire your I/O devices accordingly considering all safety issues.

This section provides diagnostic information for troubleshooting your 1746
I/O chassis using the LED’s on the front of the 1746I module. Also in this

section is information on using test modes to diagnose any problems with

the fiber-optic connections.

OFF

ON

Flashing

This LED Status

Indicates this possible cause:

Run LED On

·The I/O ring and the 1746 I/O rack are

communicating properly and the rack is

functioning.

Rack LED On

·RAM or ROM failure at power turn on.
·Device in rack failed or is not seated properly.
·Internal error in the 1746I adapter.

Rack LED Flashing

·A card type was found in the rack at power turn

on that is not supported by the 1746I module.

Ring LED On

·Connection or device has failed in the I/O ring for

a device before the 1746I in the ring.

·Power turned off at the CNC.
·Transmitter and receiver cables are reversed.

Ring LED Flashing

·Connection or device has failed in the I/O ring for

a device after the 1746I in the ring.

All LEDs Off

·Power turned off at the CNC while the ring was

up and running.

·Connection of I/O ring broken before this 1746I

module while the ring was up and running.

10A.9

1746 I/O Fault Status

10A.9.1

Troubleshooting the 1746I

Communication Module