Section 12

Wiring A-B Analog Drives

12-3

Figure 12.2

Wiring Diagram For Series 1387B Drives

21
23
25
27
34
37
39

1
3
5

48
50

8

DRIVE

DRIVE

DR RET

SHLD

1771 HTE

Encoder

Termination

Panel

7

6

5

4

Reset 3

Common 2

E-STOP 1

Motherboard (9260 and

9/290) or Processor Board

(9/230) terminal block BT1

Connection to MTB

Panel E-STOP

and E-STOP Reset

E-STOP

status

relay

Status

relay

power

User Power to

drive logic

115V ac

1387B Servo Amplifier (see note 1)

Control Power High
Control Power Low
Coast/DB Stop
Internal tie Point
High Accel/decel Rate
Internal Logic Power
Enable Input

TB2

Run Reference (+)
Run Reference (--)
Shield
Common

TB5

TB1

Fault

TB5

Velocity Command

Remote

E-STOP

Axis

Overtravel

Motor

Thermal

Overload

Drive

XFMR

Thermal

Overload

NOTE:

1. The control works only with 1387 drives

that use 115V ac and have the dynamic

braking option. Refer to Bulletin 1387 User

Manual (Publication 1387-5.0) for power

wiring and motor connection.

2. We recommend installation of this connection. Remove it if

excessive noise from chassis ground occurs.

3. The connection from the termination panel to the drive should

be as short as possible. We recommend less than 20 ft.

See

note

3

See

note 2

If your control has terminal 8,

then connect it to chassis ground.

If terminal 8 is not present on

your control, then this type of

grounding is not necessary.