Section 15A

Troubleshooting the Control

15A-21

The device number of the selected 1771 I/O Adapter device appears under

the “1771 I/O ADAPTER” heading. This will be a decimal number from

00 to 60. Following the number is the message indicating whether it is a 4,

8, 12, or 16 slot rack.

If the selected device is a 8, 12, or 16 slot rack, two or three screens may

be required to display all of the I/O data. When additional screens are

available, press and hold the [SHIFT] key and press the

[DOWN-ARROW] key to access additional screens with I/O data from

the same 1771 I/O Adapter. Cursoring down below the last row on each

screen will also access the next screen if it exists.

The 1771 I/O Adapter Diagnostic screen displays the inputs and outputs

that correspond to the terminal numbers on the 1771 I/O Adapter module.

They are listed in rows with each row representing a slot in the rack. Since

there can be 8, 16, or 32 terminals per slot, the 32 terminal slots will

require two rows of the display.

If an input or output is “ON”, its terminal number appears in inverse video.

If there is no I/O module in a slot, “EMPTY” follows the slot number.

This is a real time display, and its response is limited only by delays in

screen updates.

If more than one 1771 I/O Adapter is on the I/O Ring, a diagnostics screen

for each of these devices can be displayed. To display a diagnostics screen

for the next 1771 I/O adapter on the ring, while on the last page of the

current 1771 I/O adapter press and hold the [SHIFT] key and press the

[DOWN-ARROW] key.

Pressing the exit softkey (up arrow) at any time displays the Ring I/O

Menu screen.