Section 15A

Troubleshooting the Control

15A-33

For 9/230, 9/440 and 9/290 systems with the remote I/O option using

revision 10.01 or later firmware, both single, block transfer, and pass

through remote I/O should be available depending on your AMP, PAL or

softkey selection. The remote I/O module on the 9/260 is a standalone

module with its own I/O processor and firmware revision. The following

table illustrates some common 9/260 Remote I/O configuration errors.

9/260 Remote I/O

card Plugged into a

9/290

PAL flag $RMON Not

set in first PAL scan

$RMON is set but

block transfer is

disabled in AMP

$RMON s set and

block transfer is

enabled in AMP

9/260 RIO card

(01.01 or earlier)

9/Series Firmware

prior to release 10.01

“FCM Revision Check

Failure”displayed.

Remote I/O is

Disabled.

RIO Not Enabled

RIO is enabled for

single transfers only.

No block transfers or

pass through.

N/A

(AMP parameter did

not exist)

9/260 RIO card

(01.01 or earlier)

9/Series firmware that

supports block transfers

(10.01 or later)

“FCM Revision Check

Failure”displayed.

Remote I/O is

Disabled.

“FCM Revision Check

Failure”displayed.

Remote I/O is

Disabled.

RIO is enabled for

single transfers only.

No block transfers or

pass through.

“FCM Revision Check

Failure”displayed.

Only single transfers

enabled.

9/260 RIO card that

supports block transfer

(02.01 or later)

9/Series firmware that

supports block transfers

(10.01 or later)

“FCM Revision Check

Failure”displayed.

Remote I/O is

Disabled.

Pass through enabled.

RIO data unavailable

to PAL logic.

RIO is enabled for

single transfers. No

block transfers. Pass

through can be

enabled using softkey.

Single transfers, block

transfers, and pass

through enabled.

Softkey is not

available.