9/440HR CNC/Drive System

5B-33

Grounded vs Ungrounded Three- phase

The 9/440HR CNC/Drive comes from the factory set for three--phase

grounded systems. If your facility uses an ungrounded three--phase

360/480 volt system, you must move a jumper in the 9/440HR system

module. This jumper will connect an internal resistor that helps keep high

voltage static, that can be typical of ungrounded three phase systems, from

building up in the system module.

Jumper Setting

Three Phase Power

J27 to J26 (factory setting)

Grounded system

J27 to GND3

Ungrounded systems

Figure 5B.19

Three- phase Jumper

9/440HR System Module

Open cover

J2

6

J2

7

G

N

D

3

Wire Jumper