Section 7C

Power Distribution and Wiring Guidlines

7C-3

Figure 7C.1

Shielded Twisted-pair Cables

Signal source

Signal destination

Connect the cable shielding

through a terminal block

DO NOT connect the

cable shielding to

ground at the

signal destination

Differential input

PE

A

B

C

C

A

C

C

A

C

B

B

B

Twisted pair

Cable shielding

Exposure of the

signal cables

must be minimal

11237-I

When parallel wires are used for carrying control signals, if distances

between the noise source and the individual cables differs, one of these two

wires will be subject to stronger radiation noise than the other. However,

when a twisted--pair cable is used, both wires will be subject to equal

radiation noise regardless of the position of the noise source. This means

that equal noise voltage is applied to both of the differential input

terminals. Thus, the noise applied to the two terminals will cancel each

other and reduce the drive circuit noise.

Usually, twisted-pair shielded cables as illustrated in Figure 7C.1 are used

to transmit weak signals such as drive signals and feedback signals.

Separation of Cable Routes

Route cables with high power and low power levels (voltages and/or

currents) separately. Run cables along opposite sides of the cabinet to

minimize the influence of magnetic and electromagnetic induction noises.

Install steel sheet metal wireways between machine application cabinets.

Do not use aluminum or other non-ferrous wireways as they do not provide

magnetic shielding for the cables. Do not use dissimilar metals as this may

lead to noise buildup. In wireways, bundle wires loosely into groups

according to similar power levels and functions.

Do not run cables carrying weak signals such as drive signals and feedback

signals in parallel with the ac power cables and I/O cables. If they must be

run in parallel with each other, pass the weak signal carrying cables in

metallic conduit to protect them from the influence of magnetic and