Assigning a module address – Rockwell Automation 8520 9/Series CNC Integration Maintenance Manual Documentation Set User Manual

Page 483

Advertising
background image

Section 9A

Operator Interface

9A-16

Assigning a Module Address

Each interface assembly must have a unique node address on the I/O ring.

The node address corresponds to a unique address assigned as independent

operator panels in the I/O assignment file found in ODS (see your PAL

reference manual). The node address is selected by cutting the jumpers

located on the interface assembly(s). Figure 9A.10 shows the location of

the jumpers on the interface module.

Important: You must remove the cover from the removable operator panel

interface assembly to access the node address jumpers. Turn off power to

the interface assembly before removing the cover. Make sure to follow

proper ESD grounding procedures when working on any 9/Series

equipment.

Figure 9A.10

Removable Operator Panel Interface Assembly JP1 and JP2

Jumper Locations

Remove cover

(2 screws each side)

G

ND
12V

G

ND

5V
G

ND

5V

G

ND

5V

AC

JP1

JP2

Fiber Optic

Connections

Jumpers

L2
L1

PE

Set the node address by cutting the wire jumper(s) according to

Table 9A.E.

The node address may be any number between 00 and 03. You may have a

total of 4 interface assemblies in the 9/Series fiber optic I/O ring. The

same node address can be used for other types of modules however, each

removable operator panel interface assembly must have its own unique

address.