I/O Interface

Section 10A

10A-57

Selecting Voltage or Current Mode

The NIO4V analog module has a user selectable DIP switch setting which

allows you to configure the input channels as either current or voltage

inputs. The switches are located on the analog module board.

ATTENTION: Care should be taken to avoid connecting a

voltage source to a channel configured for current input.

Improper module operation or damage to the module can occur.

1

2

Cu

rre

nt

Cu

rre

nt

Vo

lta

ge

Switch 1 = Input Channel 0

Switch 2 = Input Channel 1

On -- Current Mode

Off -- Voltage Mode

O

N

The module has two individual switches labeled 1 and 2. These switches

control the input mode of input channel 0 and 1. A switch in the ON

position configures the channel for current input. A switch in the OFF

position configures the channel for voltage input.

Output channels are always voltage mode and can not be configured.

Wiring 1746 Analog I/O

Belden cable #8761 is recommended when wiring analog modules. Use

the following guidelines in planning the system wiring for the analog

modules:

all analog common terminals (ANL COM) are electrically connected
inside the modules. ANL COM is not connected to earth ground inside

the module.

10A.8

1746 Analog I/O