Ladder Program Basics

5-7

Input Branching

Use an input branch in your application program to allow more than one combination

of input conditions to form parallel branches (OR logic conditions). If at least one of

these parallel branches forms a true logic path, the rung logic is enabled. If none of the

parallel branches forms a true logic path, rung logic will not be enabled, the output

instruction logic will not be true, and the output will not be energized.

] [

] [

( )

A

D

C

Parallel Input Branching

] [

/

B

In the above example, either A

and

B,

or

C can provide a true logical path.

Output Branching

You can program parallel outputs on a rung to allow a true logic path to control

multiple outputs. When there is a true logic path, all parallel outputs become true.

] [

] [

( )

A

C

B

Parallel Output Branching

( )

U

E

Move

Source

S:3

Dest

N7:10

MOV

In the above example, either A

or

B provides a true logical path to all three output

instructions.