MicroLogix 1000 and PLC-500 A.I. Series Software Reference

16-6

Configuring Channel 0

It is easiest to change the Channel 0 settings while online with the processor through

Channel 1, although it is possible to change the Channel 0 settings while

communicating through Channel 0.

You can also make changes to channel configurations offline and download the new

configurations as part of the ladder logic project.

!

If you are communicating through Channel 0, and you change the parameters for the

channel, communications will terminate. In this case, you will have to reconfigure

PLC-500 A.I. to communicate at the new settings.

If you are communicating through Channel 0, and you change Channel 0 to DF1

Half-Duplex Slave, DH-485 Master, or to User Mode, communications will terminate

and cannot be restored through Channel 0. In this case, you will need to use Channel

1 to communicate with the processor, or purge the processor’s memory and

reconfigure it.

You can configure Channel 0 to communicate using:

System Mode, DF1 Full-Duplex

System Mode, DF1 Half-Duplex Limited Master (except on SLC 5/03 OS300

processors)

System Mode, DF1 Half-Duplex Slave

System Mode, DH-485 Master

User Mode, Generic ASCII

To configure Channel 0:

1.

Go online with the processor.

2.

Make sure the processor is in Program or Remote Program mode. (You can access

the configuration screens in Run or Remote Run mode, but the processor must be

in Program or Remote Program mode to accept changes.)

3.

From the Top menu bar, select

[F8]

Display

.