MicroLogix 1000 and PLC-500 A.I. Series Software Reference

5-14

The table below indicates how the operating cycle works for the four rung ladder

program discussed on pages 5-10 through 5-12. Details of program scans 999-1001 are

shown.

] [

] [

/

] [

( )

] [

] [

/

] [

/

( )

] [

] [

] [

( )

( )

I:0

B3

B3

B3

1

10

11

12

I:0

B3

B3

B3

B3

I:0

B3

B3

O:0

1

10

12

11

11

1

10

11

2

1

2

3

4

Scan

Event

Scan

Program

Initial conditions. No changes.

I:0/1 goes true, but has no

effect on the program until after the I/O scan.

999

I/O

Processor determines that external input terminal I:0/1 is On.
Bit I:0/1 in the input data file is changed from 0 to 1. Output
O:0/2 is unchanged.

Scan
1000

Program

Program is scanned. Data files are updated, as affected by bit
I:0/1. Output bit O:0/2 is changed from 0 to 1.

I/O

Output terminal O:0/2 is turned On. Input terminal I:0/1 is
unchanged.

Scan
1001

Program

Program is scanned. Bit changes that took place in the later
part of program scan 1000 are now applied to the first part of
the program.

I/O

No changes.