MicroLogix 1000 and PLC-500 A.I. Series Software Reference

19-20

When viewing a project running under PLC-500 A.I., the displayed state of inputs and

outputs on the ladder display reflects the data table values, not the actual state of the

device. Input forces affect the data table, and thus will affect the program while it is

running. Output forces occur

after

a rung has been executed, and affect only the actual

outputs, not the data table. The output state shown on the screen may not match the

state of the actual output device.

The force table functions like a filter or mask.

State of

Actual

Output
Device

Ladder

Program

Execution

State of

Actual

Input

Device

Force
Table

(Inputs)

Force
Table

(Outputs)

Data

Table

(Inputs)

Data

Table

(Outputs)

Notice that the input data table is updated before the ladder program executes and the

output data table is updated after the ladder program executes.

Using Forces

Whenever you force a contact, the word ON or OFF appears on the ladder display, just

below the instructions referencing the forced address. Remember that the ladder

program, and the reverse video used to indicate contact status, refer to the data table,

not the force table. This means that forced outputs will not be highlighted in the ladder

display unless the logic controlling the output is true.